Rehabilitating a Water Storage Tank for Easier Exterior Cleaning and Extended Service Life

Connecticut Water Authority Chooses Polysiloxane Coating to Help Meet Strict Maintenance Cycle Requirements

By Rick Goyette, Asset Protection Manager – Water Infrastructure, Sherwin-Williams Protective & Marine

restored water tank exterior

The Challenge: Restoring a 2.2-Million-Gallon Tank to Mitigate Effects of Mold and Mildew on Exterior Surfaces

The math is clear for the Aquarion Water Authority. Managing more than 100 storage tanks and rehabilitating two to three per year using available resources, Aquarion needs a 30- to 35-year cycle out of its tanks.

Reaching that long service life to enable Aquarion’s necessary maintenance cycle – and avoiding the unscheduled cost of premature restoration – requires a robust, long-lasting coating system.

An inescapable obstacle, however, is the menace of mold and mildew. The organic material commonly develops on the north side of tanks, as well as areas where shade and vegetation can trap moisture and promote biological growth. While the water inside the tank remains safe, the growth affects public perception and creates an exterior maintenance concern.

Aquarion had mold and mildew in mind when it set out to restore a reservoir tank located in the North Stamford, Connecticut, region that supplies water to the city. The 2.2-million-gallon tank – 130 feet in diameter, with a 24-foot shell height – is surrounded by a retaining wall, making it even more prone to organic surface growth. In fact, the grimy material covered the tank’s exterior coating system prior to its rehabilitation.

For the restoration, the Bridgeport, Connecticut-based water authority sought a coating that would readily enable cleaning of biological growth from tank surfaces and potentially add extra years of service life. Aquarion’s engineering and specifying team chose Sher-Loxane® 800, a polysiloxane topcoat from Sherwin-Williams Protective & Marine.

The polysiloxane technology is highly cleanable, requiring only a low-pressure wash to remove mold and mildew. It also features mildew-resistant properties and superior color and gloss retention compared to a traditional aliphatic polyurethane finish.

The rehabilitation project, completed in the spring of 2026, included restoration of the tank’s interior as well. The Stamford tank effort earned top honors in the potable water category for the 2026 Sherwin-Williams Impact Award program, which recognizes projects that demonstrate the use of high-performance coatings from Sherwin-Williams Protective & Marine.

Test Cases: Side-by-Side Coating Technologies

Aquarion is a locally governed, not-for-profit water authority providing water service to more than 735,000 people in 60 municipalities across Connecticut. It’s responsible for the operation, maintenance and long-term stewardship of one of the state’s largest water systems.

The water authority first used Sher-Loxane 800 to coat a smaller tank rehabilitated in 2025. That 180,000-gallon tank is located on a hillside where tree cover and shade are ideal for the production of mildew and biofilms. This site was also at risk for graffiti, making this coating an excellent choice for its cleaning properties.

Likewise, the North Stamford tank is also positioned against a hillside promoting elevated moisture and biofilm film growth. It’s located next to another tank that was recoated with an aliphatic polyurethane approximately a year earlier, affording Aquarion a point of comparison. Right now, it’s too early to compare coating performance, as any noticeable differences likely won’t be evident until year five or so. But having the technologies in close proximity promises to be a useful test for the authority.

What’s certain is that heavy mold buildup takes a toll on coatings. A regular program of cleaning and maintenance would help prolong the life of the system, helping Aquarion stay on track with its perpetual tank maintenance schedule. The Sher-Loxane 800 technology is expected to reduce the cleaning effort.

“There’s no magic wand of a coating that can completely prevent biological growth, so it has to be a program of maintenance,” said Gary Roberts, Senior Project Manager at engineering and construction firm CDM Smith, the specifying firm for the project. “But hopefully this coating is one key component of that. We have a nice side-by-side comparison to work from.”

Aquarion is considering moving to a regular cleaning cycle, especially because the Sher-Loxane 800 coating makes cleaning easier and is designed to support longer rehabilitation intervals. Such a program would align with the Connecticut Department of Public Health, which has started to place greater emphasis on tank appearance, though it hasn’t implemented formal requirements.

“Tank aesthetics is important to us and the public,” said Mark Fois, Senior Engineer, Aquarion. “We want to ensure our structures stay bright and clean over time, for the sake of both appearance and longevity. We’re looking into an every-other-year washing program since the Sher-Loxane 800 coating can accommodate it.”

Figure 1. The Stamford, Connecticut, water tank is surrounded by a retaining wall and some vegetation, which contributed to the mold and mildew evident on its exterior coating system prior to the tank’s rehabilitation.

Figure 2. The restored tank exterior is coated with Sher-Loxane® 800, a polysiloxane topcoat chosen by the Aquarion Water Authority first for its easy cleanability of biological growth, and also for its mildew resistance and superior color and gloss retention.

Figure 3. The tank’s interior was at the end of its life cycle, showing significant signs of corrosion.

The Solution: Polysiloxane Technology for Longer-Lasting Water Tank Protection

Applicators from R.J. Forbes Painting executed the exterior rehabilitation partially in the fall months of 2025, with the remainder completed in the spring of 2026 and the tank placed back in service in early April 2026, before peak water demand returned. The work schedule coincided with what is typically lower demand in winter. Interior restoration took place in the fall of 2025, with completion in late November.

Restoration of the Stamford tank’s mold-covered exterior surface (Figure 1) began with a commercial blast cleaning to the SSPC SP-6 level, essentially removing all the visible oil, grease, dust, dirt, mill scale, rust and old coatings. Applicators then applied Corothane® I GalvaPac 1K, a single-compound, moisture-curing urethane zinc-rich primer, at 3 to 4 mils dry film thickness (DFT).

They followed with a stripe coat of Macropoxy® 646 Fast Cure followed by a full intermediate coat at 5 to 7 mils DFT. The two-component, fast-dry, low volatile organic compound (VOC) rating, high-build epoxy is designed for quick recoating to assist demanding production schedules.

Then came the topcoat of Sher-Loxane 800, applied at 4 to 6 mils DFT. The polysiloxane coating combines the properties of both a high-performance epoxy and a polyurethane to enable the durability of the former and the flexibility of the latter in the same application.

“The coating’s higher build and finish will help the tank stay cleaner for longer, and make it much easier to clean as well,” said Ross Forbes, Owner of R.J. Forbes Painting, the contractor on the project. “It provides both a nice finish and added protection.”

Contractors applied the coatings almost entirely using spray equipment, with some brushing and rolling where needed. The finished exterior (Figure 2) matched the cream color of the tank next to it.

Cold weather posed a challenge on the exterior job. And it’s here that another benefit of Sher-Loxane 800 came to the fore: its ability to perform at lower temperatures. Applicators used hardeners based on environmental conditions to give the coating a larger temperature range than aliphatic polyurethane alternatives.

“This gave us flexibility in applying the coating,” said Forbes. “It helped us get the topcoats going quicker than would have been possible using an aliphatic polyurethane.”

Interior Restoration: Using Handy Paint Cartridges in the Critical Last Step

The Stamford tank’s interior had reached its end-of-life cycle, showing significant signs of corrosion (Figure 3). Rehabilitation began with an abrasive blast to the SSPC SP 10 Near-White Metal Blast Cleaning standard, leaving a steel surface free of coatings and residues with a minimum 2-mil profile to promote adhesion.

The process exposed considerable metal deterioration and pitting in the rafters and columns. Crewmembers from R.J. Forbes replaced some steel and used Sherwin-Williams Steel-Seam™ FT910 Epoxy Patching and Surfacing Compound to bring other steel members to an even plane.

Applicators then moved to a standard coating system of primer, stripe coat and lining in accordance with AWWA D102 Interior Coating System (ICS) #3. Just as with the exterior work to follow, the primer consisted of Corothane I GalvaPac 1K, applied in a dark gray coat at 3 to 4 mils DFT. In the stripe coating, the crew brushed Sherplate® 600 – a two-component potable water epoxy lining – on every seam, weld, crevice and irregular surface. Depending on the surface, applicators applied the stripe coat at 4 to 6 mils DFT. At the completion of the primer and stripe coat stages (Figure 4), the interior was prepared for the lining application.

For the lining on the immersed floor and wall areas of the tank, Aquarion chose Sherplate® PW applied in white to a thickness of 25 to 30 mils DFT in a single coat (Figure 5). Sherplate PW is a two-component, edge retentive, low-VOC, 100% ultra-high-solids epoxy amine coating. It provides corrosion resistance for these vital areas of the tank, as well as excellent edge retention.

For protection on the numerous hard angles and edges that make up the tank ceiling’s structure, applicators applied two coats of Sherplate 600 at 4 to 6 mils DFT each to ensure greater coverage and longer service. The coating has the highest performing edge protection per MIL-PRF-23236. Applicators used a cream color for the initial Sherplate 600 coat (Figure 6), which provided a helpful contrast for identifying any bleed-through or missed areas when applying the second white-tinted coat to ensure full coverage.

The R.J. Forbes team successfully met challenges during the interior restoration, including removing, storing, repairing and reinstalling the tank’s baffle curtain without damaging the new coating. They overcame another obstacle thanks to a handy Sherwin-Williams technology: paint cartridges. At the project’s start, the crew had to cut door sheet in the tank’s side to enable equipment access and removal of the baffle curtain. Near the project’s end, they reinstalled the steel plate to close the door sheet opening and used cartridges of Sherplate PW to coat the weld repairs and create a continuous lining.

The cartridges saved the crew time and money. They consist of two connected caulk tubes that are loaded into a double-barreled caulk gun in which the contents from each tube – Part A on one side and Part B on the other – mix at the tip. Applicators can mix only what they need and then store the cartridges for future use. Without the cartridges, applicators would have had to use plural component equipment, which would have required mixing more paint than was needed and performing extensive equipment cleaning just to coat a small area. Sherwin-Williams also offers burst pouches that serve the same purpose as cartridges.

The Results: A Potable Water Tank Solution for Decades to Come

Throughout the project, intensive third-party inspections took place to ensure R.J. Forbes applied all coatings properly and to the right thickness.

Given the success of the application, Aquarion planned to use Sher-Loxane 800 as the exterior coating on two more tank restorations in the fall of 2026.

As the industry continues looking for improved outside coating system solutions, polysiloxanes like Sher-Loxane 800 appear to be a good fit. The coating gives tank owners a weapon against the scourge of mold and mildew, enabling them to remove the grime with a low-pressure wash before it can damage the coating surface and reduce service life.

 

ABOUT THE AUTHOR

Rick Goyette is an Asset Protection Manager – Water Infrastructure for Sherwin-Williams Protective & Marine. He has been with the company for 12 years and has more than 25 years of experience in the coatings industry. His current geographic area of responsibility covers all six New England states. He is an AMPP Certified Coatings Inspector, as well as an AMPP Concrete Coatings Inspector, Level 2, and is a member of numerous water and wastewater organizations throughout the New England region. Contact: Rick.R.Goyette@sherwin.com

Figure 4. Rehabilitation began with an abrasive blast to the SSPC SP 10 Near-White Metal Blast Cleaning standard. That was followed by steel resurfacing or replacement; application of the primer, Corothane® I GalvaPac 1K; and stripe coating using Sherplate® 600.

Figure 5. For the lining, crewmembers applied two coats of Sherplate® 600 to the tank’s ceiling and a full coat of Sherplate PW to its floor and walls. Both products provide corrosion resistance and excellent edge retention.

Figure 6. For the tank’s ceiling, applicators first applied a cream-tinted coat of Sherplate 600 (shown) to provide a helpful contrast for confirming full coverage when applying the white-tinted topcoat.


Our Water & Wastewater Expertise

Explore our industry solutions and technology to help protect your assets.

LEARN MORE

Product Lookup

Find out more about our innovative coatings for a variety of industries.

FIND A PRODUCT

Let's Talk

We'd love to discuss your needs for time-tested, smarter asset protection.

CONTACT US
Back To Top